particle/ft³ | ||||||
Class | 0.1 µm | 0.2 µm | 0.3 µm | >0.5 µm | >1 µm | >5 µm |
1 |
35 |
7 |
3 |
1 |
|
|
10 |
350 |
75 |
30 |
10 |
1 |
|
100 |
3500 |
750 |
300 |
100 |
10 |
1 |
1,000 |
|
|
|
1,000 |
100 |
10 |
10,000 |
|
|
|
10,000 |
1,000 |
100 |
100,000 |
|
|
|
100,000 |
10,000 |
1,000 |
NOTE: US FED STD 209E was canceled November 29, 2001.
particle/m³ | ||||||
Class | 0.1 µm | 0.2 µm | 0.3 µm | 0.5 µm | 1 µm | 5 µm |
ISO 1 |
10 |
2 |
|
|
|
|
ISO 2 |
100 |
24 |
10 |
4 |
|
|
ISO 3 |
1,000 |
237 |
102 |
35 |
8 |
|
ISO 4 |
10,000 |
2,370 |
1,020 |
352 |
83 |
|
ISO 5 |
100,000 |
23,700 |
10,200 |
3,520 |
832 |
29 |
ISO 6 |
1,000,000 |
237,000 |
102,000 |
35,200 |
8,320 |
293 |
ISO 7 |
|
|
|
352,000 |
83,200 |
2,930 |
ISO 8 |
|
|
|
3,520,000 |
832,000 |
29,300 |
ISO 9 |
|
|
|
35,200,000 |
8,320,000 |
293,000 |
ISO 14644-1 | FED STD 209E |
ISO 3 | 1 |
ISO 4 | 10 |
ISO 5 | 100 |
ISO 6 | 1,000 |
ISO 7 | 10,000 |
ISO 8 | 100,000 |